Get Acrobat Reader Ductile Iron Flange for R6904, R6905, and R6906
Installation
Convert To Metric Units
Size
(in.)
D E F G H Flange
Thickness
J Bolt Size** for
connecting Expansion
Joints to CPI & HVAC
Holes Thread B.C.* Holes Thread B.C.* B.C. Class 125 & 150
ANSI Flanges***
1 4 1/2-13 3 1/8 4 5/16-18 3 1/8 1/4 5 1/8 4 1/4 5/16 6 1/2 - 13 x 1
1 1/2 13 7/8 3 7/8 5 7/8 5 11/32 6 3/4 1/2 - 13 x 1 1/4
2 5/8-11 4 3/4 4 3/4 3/8 6 7/8 6 7/16 8 1/2 5/8 - 11 x 1 1/2
2 1/2 5 1/2 - - - 8 1/8 7 1/2 9 3/8 5/8 - 11 x 1 3/4
3 6 4 5/16-18 6 8 3/4 7 1/2 10 5/8 - 11 x 1 3/4
4 8 7 1/2 8 7 1/2 9 7/8 9 5/8 11 1/8 5/8 - 11 x 2
5 3/4-10 8 1/2 - - - 1/2 11 1/2 10 3/4 13 3/4 - 10 x 2
6 9 1/2 8 3/8-16 9 1/2 12 1/2 11 14 3/4 - 10 x 2
8 11 3/4 - - - 14 3/4 13 1/2 15/16 16 1/4 3/4 - 10 x 2 1/2
10 12 7/8-9 14 1/4 17 1/2 16 1 19 7/8 - 9 x 2 1/2
12 17 5/8 20 1/2 19 22 7/8 - 9 x 2 1/2
14 1-8 18 3/4 CF 24 11/64 21 1 3/16 27 5/16 CF
16 16 21 1/4 27 9/16 23 1/2 31 1/2
18 1 1/8-7 22 3/4 29 25 32 29/32
20 20 25 31 1/2 27 1/2 35 7/16
24 1 1/4-7 29 1/5 35 29/32 32 1 11/32 39 27/32
All Dimensions in inches.
* Bolt circle same as 125 and 150 lb. ANSI standard.
** Add bolt diameter to length for stud bolts.
*** Lap-joint flanges may require 1/4" longer bolt in some instances.
CF = Consult Factory

Warning: If components show significant deterioration to abrasion, damage, or corrosion, the assembly should be removed from service. Failure to periodically perform inspection for abrasion, damage, or corrosion may lead to failure and/or rupture of the assembly resulting in property damage, serious personal injury, or death.

Bolt Torque Information
Bolts should be tightened using the following torques as a guide and with well lubricated threads.

Nominal Expansion Joint
Size (inches)
1 1 1/2 2 2 1/2 3 4 5 6 8 10 12
Flange Bolt Torque
ft.-lbs.
10 15 25 30 40 30 40 60 75 70 75
No. of Holes
Per Flange
4 4 4 4 4 8 8 8 8 12 12
Note: The values in this table are a guide. In some instances, higher torque may be required. However, excessive torque should be avoided. Do not exceed twice the given values.