for Resistoflex Plastic-Lined Pipe and Fittings

F x F = Fixed x Fixed
F x R = Fixed x Rotatable
R x R = Rotatable x Rotatable

Use high-strength A193 B7 machine bolts or studs. Use proper torque values.
Convert To English Units
ANSI Class 150 bolt and stud length requirements
(All dimensions in millimeters)
Flange
Size
Stud Length Bolt Length
F x F F x R R x R F x F F x R R x R
25 76 83 83 64 70 70
40 83 89 89 70 76 76
50 102 102 108 83 83 89
65 102 N/A N/A 83 N/A N/A
80 108 114 114 89 95 102
100 108 114 114 89 95 102
150 127 127 133 108 108 114
200 127 133 140 108 114 121
250 140 146 152 114 121 133
300 140 146 159 121 127 140

ANSI Class 300 bolt and stud length requirements
(All dimensions in millimeters)
Flange
Size
Stud Length Bolt Length
F x F F x R R x R F x F F x R R x R
25 89 95 95 76 83 83
40 102 108 114 89 95 95
50 102 102 108 83 89 95
80 121 133 133 108 121 121
100 127 140 140 114 127 127
150 140 146 152 121 133 133
200 159 178 178 133 146 159
250 178 184 197 152 159 171
300 197 203 210 165 171 178
Note: Bolt/Stud lengths for both Class 150 and 300 are calculated to include two threads past the nut, then rounded to the nearest 6.4mm, to result in a commercially available length. Lengths include flat washers on both sides.



"This page is a machine translation of the source page, which is written in
English. This translation is intended to provide a general idea of the